HYPER MIST & SPRINKLER SYSTEM

Oral-Ship Construction, Stability, Ship Safety and Environment Protection (FUNCTION –3)

The following questions came from WhatsApp group where candidates posts the question right after they had finished their oral exam.
  • Should have fitted in every cargo ship of 2000 GRT and above.
  • Should have fitted in the machinery space of 500 m³ in volume and above.
  • It must have an independent power source.
  • The number and arrangement should be such as to ensure distribution of water at least 5 l/m²/min.
  • Should have a manual as well as an auto-release mechanism.
  • Activation shall give a visual and audible alarm in the protected space.
  • Should have fitted in every cargo ship of 2000 GRT and above.
  • Should have fitted in the machinery space of 500 m³ in volume and above.
  • It must have an independent power source.
  • It shall be resistant to corrosion by the marine atmosphere.
  • It shall come into operation within the temperature range from 68°C to 79°C.
  • Each sprinkler head is to cover about 16 m² of area.
  • Heads are to be spaced not more than 4 m apart and 2 m from the vertical wall.
  • Each sprinkler head should be capable of discharging at 100 liters/min.

HYPER MIST

SPRINKLER

It uses fresh water.

It uses sea water.

It activates when two different detectors are activated.

It has a temperature bulb.

More pressure is required.

Less pressure is required.

The droplet size is small.

Droplet size is bigger than hyper mist.